ELECTRICAL SPECIFICATIONS
DC Voltage Measurement
Range Resolution Accuracy
400mV
˜
˜
400V
0.1mV
˜
˜
0.1V
± (0.5% + 4 digits)
1000V
1V
± (0.8% + 10 digits)
Overload Protection:
1000V
AC Voltage Measurement
Range Resolution Accuracy
400mV
˜
˜
750V
0.1mV
˜
˜
1V
± (2.0% + 5 digits)
Overload Protection:
750V RMS
Frequency Response:
40 to 400 Hz
Minimum Voltage for Frequency Measurement:
200mV
Response:
Averaging
DC Current Measurement
Range Resolution Accuracy
400µA
0.1µA
± (1.2% + 3 digits)
2000µA
1µA
Overload Protection:
Voltage:
600V RMS
Current:
2000µA
AC Current Measurement
Range Resolution Accuracy
400µA
0.1µA
± (2.0% + 5 digits)
2000µA
1µA
± (1.5% + 5 digits)
40A
0.01A
± (2.9% + 15 digits)
400A
0.1A
± (1.9% + 8 digits)
Overload Protection:
Voltage:
600V RMS
Current:
2000µA
Frequency:
45 to 400Hz
Minimum Current for Frequency Measurement:
400µA or 20A
Response:
Averaging
Resistance Measurement
Range Resolution Accuracy
400
˜
4M
˜
4M
˜
0.1
˜
0.001M
˜
0.001M
˜
± (1.0% + 4 digits)
40M
0.01M
± (2.0% + 4 digits)
Overload Protection:
600V RMS
Capacitance Measurement
Range Resolution Accuracy
40nF
˜
4000µF
˜
4000µF
˜
0.01nF
˜
1µF
˜
1µF
˜
± (3.5% + 6 digits)
Overload Protection:
600V RMS
Frequency Measurement
Range Resolution Accuracy
99.99Hz
˜
499.9kHz
˜
499.9kHz
˜
0.01Hz
˜
0.1kHz
˜
0.1kHz
˜
± (0.1% + 4 digits)
Overload Protection:
600V RMS
Sensitivity:
1.8V RMS